motor protection GV2ME06 GV2

product-image-0
50

motor protection GV2ME06 GV2

$26.49 $52.98

Start-stop control by push-button guaranteed for 100 000 cycles AC-3. It provides a thermal-magnetic protection with a thermal setting range…

Category: Others
SKU: QNLJ663661291216

Start-stop control by push-button guaranteed for 100 000 cycles AC-3. It provides a thermal-magnetic protection with a thermal setting range 1-1.6A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX). Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
Specifications
Main
Range
TeSys Deca
Product name
TeSys GV2
Product or component type
Motor circuit breaker
Device short name
GV2ME
Device application
Motor protection
Trip unit technology
Thermal-magnetic
Complementary
Poles description
3P
Network type
AC
Utilisation category
Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
AC-3e conforming to IEC 60947-4-1
Network frequency
50/60 Hz conforming to IEC 60947-2
Motor power kW
0.37 kW at 400/415 V AC 50/60 Hz
0.55 kW at 400/415 V AC 50/60 Hz
0.37 kW at 500 V AC 50/60 Hz
0.55 kW at 500 V AC 50/60 Hz
0.75 kW at 500 V AC 50/60 Hz
0.75 kW at 690 V AC 50/60 Hz
1.1 kW at 690 V AC 50/60 Hz
Breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control type
Push-button
[In] rated current
1.6 A
Thermal protection adjustment range
11.6 A conforming to IEC 60947-2
Magnetic tripping current
26.2 A
[Ith] conventional free air thermal current
1.6 A conforming to IEC 60947-2
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
Phase failure sensitivity
Yes conforming to IEC 60947-4-1
Suitability for isolation
Yes conforming to IEC 60947-1
Power dissipation per pole
2.5 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles for AC-3 at 415 V In
100000 cycles for AC-3e at 415 V In
Rated duty
Uninterrupted conforming to IEC 60947-4-1
Connections terminals
Power circuit: screw clamp terminal 2 cable(s) 16 mm solid
Power circuit: screw clamp terminal 2 cable(s) 1.56 mm flexible without cable end
Power circuit: screw clamp terminal 2 cable(s) 14 mm flexible with cable end
Tightening torque
1.7 N.m on screw clamp terminal
Fixing mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)
Mounting position
Horizontal
Vertical
Width
45 mm
Height
89 mm
Depth
78.5 mm
Product weight
0.26 kg
Colour
Dark grey

Reviews (0)

There are no reviews yet.

Your Review